Id: arxiv/2602.12293 Url: https://arxiv.org/abs/2602.12293 Tags: math.OC, eess.SY Score: 0 Title: Real-Time Dynamic N-1 Screening: Identifying High-Risk Lines and Transformers After Common Faults Domain: math.OC Source: arxiv Authors: Ayrton Almada, Laurent Pagnier, Igal Goldshtein, Saif R. Kazi, Michael, Chertkov Reviews: 0 Subject: math.OC Category: research Comments: 0 Disputed: false Division: math Mentions: 0 Discussed: 0 Published: 2026-01-31 Page: https://delphi.science/r/arxiv/2602.12293 Power system operators routinely perform N-1 contingency analysis, yet conventional tools provide limited guidance on which lines or transformers deserve heightened attention during fast post-fault transients. In particular, static screening does not reveal whether (1) the same faulted line repeatedly triggers severe downstream overloads, or (2) a specific transformer emerges as vulnerable across many distinct fault scenarios. This paper introduces a real-time dynamic N-1 screening framework that addresses this gap by estimating, for each counterfactual single-phase transmission fault, the…